Type: PowerIT CSS-SW.7.11
The enclosure is divided into two compartments, one for the MV switchgear and LV switchboard and one for the distribution transformer. The weight of the CSS without electrical equipment is 3400 kg.
Dimensions (LxWxH)
Enclosure - 6 degree roof: 3634 x 2434 x 2558 mm
Transformer compartment: 2160 x 1273 x 2239 mm
Max equipment
Transformer:
- 1600 kVA hermetically sealed oil transformer.
MV Equipment:
- 6 panel SafePlus 12 / 24 kV
- MV transformer cables are as standard 25 mm2 Cu. If the Tee-off is with a vacuum circuit breaker 95 mm2 Al cables will be installed.
LV Equipment:
- LVS3-20M
....... 20 x 400 A InLine fuse switches or
....... 12 x 400 A Kabeldon fuse switches
- LV cables for a 1600 kVA transformer are 4 x 300 mm2 per phase.