Type: PowerIT CSS-SW.6.11
The enclosure is divided into two compartments, one for the MV switchgear and LV switchboard and one for the distribution transformer. The weight of the CSS without electrical equipment is 2975 kg.
Dimensions (LxWxH)
Enclosure (6 degree roof): 3634 x 2134 x 2342 mm
Transformer compartment: 1860 x 1273 x 2039 mm
Max equipment
Transformer:
- 1000 kVA hermetically sealed oil transformer
MV Equipment:
- 5 panel SafePlus 12 / 24 kV
- MV transformer cables are as standard 25 mm2 Cu. If the Tee-off is with a vacuum circuit breaker 95 mm2 Al cables will be installed.
LV Equipment:
- LVS3-16M
.......16 x 400 A InLine fuse switches
.......10 x 400 A Kabeldon fuse switches
- LV cables for a 1000 kVA transformer are 3 x 240 mm2 per phase.